Does the owner sign the fire alarm inspection report?

Short answer

The Ontario Fire Code does not mention an owner signature. It makes the owner responsible for having the system tested by a qualified person and for keeping the records. A published summary of the 2019 edition of CAN/ULC-S536 says the owner signs off once deficiencies are resolved.

Edition: CAN/ULC-S536-2019Updated 2026-11-22Source: Ontario Fire Code, O. Reg. 213/07, on e-Laws

What is the owner responsible for?

Article 1.2.1.1 of Division A of the Ontario Fire Code says the owner carries out the Code unless it says otherwise. For a fire alarm system that includes:

  • 6.3.2.1.(1): using a qualified person for the annual tests and inspections.
  • 6.3.2.2.(3): keeping a current description of the system in the building.
  • 6.3.2.2.(4): keeping a record for each device, component and circuit.
  • 6.3.2.2.(5): recording whether the monitoring station received the test signals, where the system is monitored.

What does sign-off after deficiencies mean?

Tap Report's summary of the 2019 edition says the owner formally signs off after deficiencies are resolved, and the signed document is kept. Confirm the wording in your copy of the standard.

How long are the records kept?

Article 1.1.2.2 of the Fire Code sets two conditions, and both apply:

  • At least two years after the record is made.
  • Always the most recent record and the one before it.

The initial verification report for a system installed after 21 November 2007 is kept for the life of the system.

Can the records be electronic?

Yes. Sentence 1.1.2.1.(4) says electronic records that can be made readily available to the Chief Fire Official on request are deemed to comply with the rule to keep records at the building.

Sources

Read on 2026-11-22. This page is a summary, not legal advice. The Fire Code and the standard govern.

Questions

Who signs the inspection report?
The technician who carried out the inspection signs it. A published summary of the 2019 edition adds an owner sign-off after deficiencies are resolved.
How long must the owner keep the report?
At least two years, and always the most recent report and the one before it. That is Article 1.1.2.2 of the Ontario Fire Code.
Where are the records kept?
At the building. Electronic records that can be produced on request are accepted.