Battery standby calculator
Enter the panel currents and durations to get the amp-hours.
Required capacity
- Standby 0.45 A x 24 h
- 10.80 Ah
- Alarm 2.10 A x 30 min
- 1.05 Ah
- Safety factor
- x 1.2
- Total, rounded up
- 14.22 Ah
Next common battery size: 18 Ah
Updated 2026-11-22Result rounded up to 0.01 Ah
How it is calculated
(standby A x standby h + alarm A x alarm h) x safety factor
Durations depend on the building code and the system type. Use the values from your system design; the calculator does not choose them. The installer's code requirements govern.
The total is rounded up to the next hundredth of an amp-hour, never down. Sizing is not the same as testing: the annual inspection measures the installed battery under load. See battery load testing.
Questions
- How do I size a fire alarm battery?
- Multiply the standby current by the standby hours, add the alarm current multiplied by the alarm time in hours, then multiply the sum by a safety factor. The result is the capacity in amp-hours.
- Is this the battery load test?
- No. This sizes a battery. The load test measures the installed battery and goes in the report.
- Where do I find the currents?
- In the panel manufacturer's battery calculation sheet, per module and device.
- Which standby and alarm times do I use?
- The ones your building code and system design call for. The calculator does not choose them, and the installer's code requirements govern.